CU240B-2 (CU240B-2 ve CU240B-2 DP)
Ön ayar 7'de jog 1 ve jog 2 hız değerleri p1058 (fabrika 150 dev/dk) ve p1059 (fabrika −150 dev/dk) parametreleridir (PDF 108).
| p0015 | Kılavuzdaki ad | BOP-2 adı | Ana setpoint (p1070[0]) |
|---|---|---|---|
| 7 | Fieldbus with data set switchover (PROFIBUS cihazın fabrika ayarı) | FB cdS | 2050[1] |
| 9 | Standard I/O with MOP | Std MoP | 1050 |
| 12 | Standard I/O with analog setpoint (USS cihazın fabrika ayarı) | Std ASP | 755[0] |
| 17 | 2-wire (forw/backw1) | 2-wIrE 1 | 755[0] |
| 18 | 2-wire (forw/backw2) | 2-wIrE 2 | 755[0] |
| 19 | 3-wire (enable/forw/backw) | 3-wIrE 1 | 755[0] |
| 20 | 3-wire (enable/on/reverse) | 3-wIrE 2 | 755[0] |
| 21 | USS fieldbus | FB USS | 2050[1] |
CU240E-2 (DP, PN ve F varyantları dahil)
| p0015 | Kılavuzdaki ad | BOP-2 adı | Ana setpoint (p1070) |
|---|---|---|---|
| 1 | Conveyor technology with 2 fixed frequencies | coN 2 SP | [0] = 1024 |
| 2 | Conveyor systems with Basic Safety | coN SAFE | [0] = 1024 |
| 3 | Conveyor systems with 4 fixed frequencies | coN 4 SP | [0] = 1024 |
| 4 | Conveyor system with fieldbus | coN Fb | [0] = 2050[1] |
| 5 | Conveyor systems with fieldbus and Basic Safety | coN Fb S | [0] = 2050[1] |
| 6 | Fieldbus with Extended Safety | Fb SAFE | [0] = 2050[1] |
| 7 | Fieldbus with data set switchover (PROFIBUS/PROFINET cihazın fabrika ayarı) | FB cdS | [0] = 2050[1] |
| 8 | MOP with Basic Safety | MoP SAFE | [0] = 1050 |
| 9 | Standard I/O with MOP | Std MoP | [0] = 1050 |
| 12 | Standard I/O with analog setpoint (USS cihazın fabrika ayarı) | Std ASP | [0] = 755[0] |
| 13 | Standard I/O with analog setpoint and safety | ASPS | [0] = 755[0] |
| 14 | Process industry with fieldbus | Proc Fb | [0] = 2050[1], [1] = 1050 |
| 15 | Process industry | Proc | [0] = 755[0], [1] = 1050 |
| 17 | 2-wire (forw/backw1) | 2-wIrE 1 | [0] = 755[0] |
| 18 | 2-wire (forw/backw2) | 2-wIrE 2 | [0] = 755[0] |
| 19 | 3-wire (enable/forw/backw) | 3-wIrE 1 | [0] = 755[0] |
| 20 | 3-wire (enable/on/reverse) | 3-wIrE 2 | [0] = 755[0] |
| 21 | USS fieldbus | FB USS | [0] = 2050[1] |
Ön ayar 12, 17, 18, 19, 20: giriş atamaları
CU240B-2'de bu ön ayarlarda DO0 arıza, AO0 gerçek hızdır; CU240E-2'de ön ayar 12, 17, 18, 19 ve 20'de ayrıca DO1 alarm ve AO1 gerçek akımdır (PDF 121, 123–125); CU240B-2'de DO1 ve AO1 yoktur (PDF 109). Kılavuzun CU240B-2 ön ayar 19 ve 20 şeklinde DI3 '16' numaralı terminal olarak çizilmiştir, oysa CU240B-2 terminal şeridinde DI3 terminal 8'dir (PDF 104, 110): terminal numarasını şerit etiketinden doğrulayın. Kalan ön ayarların terminal ayrıntıları için kılavuz sayfalarına bakın (CU240B-2: PDF 108–110, CU240E-2: PDF 116–125).
| Ön ayar | DI0 | DI1 | DI2 | Diğer |
|---|---|---|---|---|
| 12 Std ASP | ON/OFF1 | Ters yön (reversing) | Arıza onayı | AI0 hız setpoint'i |
| 17 2-wIrE 1 | ON/OFF1 saat yönü | ON/OFF saat yönü tersi | Arıza onayı | AI0 hız setpoint'i |
| 18 2-wIrE 2 | ON/OFF1 saat yönü | ON/OFF saat yönü tersi | Arıza onayı | AI0 hız setpoint'i (CU240B-2 şekli, PDF 109) |
| 19 3-wIrE 1 | Enable/OFF1 | ON saat yönü | ON saat yönü tersi | DI3: arıza onayı (CU240E-2'de DI4, terminal 16); AI0 hız setpoint'i (CU240B-2 şekli PDF 110; CU240E-2 şekli PDF 124–125) |
| 20 3-wIrE 2 | Enable/OFF1 | ON | Ters yön | DI3: arıza onayı (CU240E-2'de DI4, terminal 16); AI0 hız setpoint'i (CU240B-2 şekli PDF 110; CU240E-2 şekli PDF 124–125) |
Kılavuz sayfaları
- 4.5.5 Default setting 7 and 9 (CU240B-2) ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 108
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10 - 4.5.5 Default setting 12, 17, 18 (CU240B-2) ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 109
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10 - 4.5.5 Default setting 19, 20, 21 (CU240B-2) ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 110
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10 - 4.5.8 Default settings 1, 2 (CU240E-2) ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 116
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10 - 4.5.8 Default settings 3, 4 (CU240E-2) ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 117
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10 - 4.5.8 Default settings 5, 6 (CU240E-2) ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 118
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10 - 4.5.8 Default setting 7 (CU240E-2) ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 119
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10 - 4.5.8 Default settings 8, 9 (CU240E-2) ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 120
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10 - 4.5.8 Default setting 12, 13 (CU240E-2) ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 121
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10 - 4.5.8 Default setting 14 (CU240E-2) ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 122
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10 - 4.5.8 Default settings 15, 17 (CU240E-2) ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 123
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10 - 4.5.8 Default settings 18, 19 (CU240E-2) ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 124
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10 - 4.5.8 Default settings 20, 21 (CU240E-2) ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 125
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10 - 6.4.1 Two-wire control, method 1 ↗SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units — Operating Instructions · PDF 206
04/2018 Edition · A5E34259001B AF · FW V4.7 SP10
Kılavuzdan sadeleştirilmiş özettir; sahada denenmiş uygulama onayı değildir. PDF sayfası dosyadaki sırayı, bölüm bilgisi kılavuzdaki başlığı veya basılı sayfayı gösterir.